ABB RELION 620 Series Technical Manual page 62

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
Parameter
Values (Range)
Amplitude corr. B
0.900...1.100
Amplitude corr. C
0.900...1.100
Voltage input type
1=Voltage trafo
3=CVD sensor
Table 10:
Analog input settings, residual voltage
Parameter
Values (Range)
Secondary voltage
60...210
Primary voltage
0.100...440.000
Amplitude corr.
0.900...1.100
Table 11:
Authorization settings
Parameter
Values (Range)
Local override
0=False
1=True
Remote override
0=False
1=True
Local viewer
Local operator
Local engineer
Local admin
Remote viewer
Remote operator
Remote engineer
Remote admin
Authority logging
1=None
2=Configuration
change
3=Setting group
4=Setting group,
control
5=Settings edit
6=All
1) Authorization override is disabled, LHMI password must be entered.
2) Authorization override is enabled, LHMI password is not asked.
3) Authorization override is disabled, communication tools ask password to enter the protection relay.
4) Authorization override is enabled, communication tools do not need password to enter the protection relay, except for WHMI which always
requires it.
56
Unit
Step
0.001
0.001
Unit
Step
V
1
kV
0.001
0.001
Unit
Step
1)
2)
3)
4)
Default
Description
1.000
Phase B Voltage phasor magnitude correction
of an external voltage transformer
1.000
Phase C Voltage phasor magnitude correction
of an external voltage transformer
1=Voltage trafo
Type of the voltage input
Default
Description
100
Secondary voltage
11.547
Primary voltage
1.000
Amplitude correction
Default
Description
1=True
Disable authority
1=True
Disable authority
0
Set password
0
Set password
0
Set password
0
Set password
0
Set password
0
Set password
0
Set password
0
Set password
4=Setting group,
Authority logging level
control
1MAC504801-IB E
620 series ANSI
Technical Manual