Section 4
Protection functions
4.7.2.4
504

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of 78 can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
I
1
V
1
I
2
BLOCK
DISABLE
GUID-5DDF20C9-555D-464E-850B-28F80803D4B6 V1 EN
Figure 240:
Functional module diagram
Impedance calculation
This module calculates the positive-sequence impedance (Z1) using positive-sequence
voltage and current. For the module to calculate impedance it is required that the positive-
sequence current is above Min Ps Seq current setting and the negative-sequence current
is below the Max Ng Seq current setting.
The calculated positive-sequence impedance amplitude Z1_AMPL and angle
Z1_ANGLE are available in ohms and degrees, respectively, in the Monitored data view.
The calculated impedance is converted to ohms as the operating
characteristics are defined with the ohm settings.
Out of step detection
The operating characteristic is a circular offset mho on the impedance plane with two pair
of blinders. The mho characteristic is defined with the Forward reach, Reverse reach, and
Impedance angle settings. Forward reach defines the impedance from the origin to the
edge of circle on the top side. Reverse reach defines the impedance from the origin to the
edge of the circle on the bottom side. The diameter of the mho characteristics is the sum of
Forward reach and Reverse reach settings. Two sets of blinders are defined by Inner
Impedance
Out of step
calculation
detection
Blocking
logic
1MAC504801-IB E
TRIP
SWING
OSB
OSB_Z2
SWING_TR
620 series ANSI
Technical Manual