Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.5.1.7
Table 314:
49F Group settings
Parameter
Values (Range)
Env temperature set
-50...100
Current multiplier
1...5
Current reference
0.05...4.00
Temperature raise
0.0...200.0
Time constant
60...60000
Maximum temperature
20.0...200.0
Alarm value
20.0...150.0
Reclose temperature
20.0...150.0
Table 315:
49F Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Initial temperature
-50.0...100.0
4.5.1.8
620 series ANSI
Technical Manual

Settings

Unit
Step
°C
1
1
xIn
0.01
°C
0.1
s
1
°C
0.1
°C
0.1
°C
0.1
Unit
Step
°C
0.1

Monitored data

Table 316:
49F Monitored data
Name
Type
TEMP
FLOAT32
TEMP_RL
FLOAT32
T_TRIP
INT32
T_ENA_CLOSE
INT32
49F
Enum
Default
Description
40
Ambient temperature used when AmbiSens is
set to Off
1
Current multiplier when function is used for
parallel lines
1.00
The load current leading to Temperature raise
temperature
75.0
End temperature rise above ambient
2700
Time constant of the line in seconds.
90.0
Temperature level for trip
80.0
Temperature level for pickup (alarm)
70.0
Temperature for reset of block reclose after trip
Default
Description
5=disable
Operation Disable / Enable
0.0
Temperature raise above ambient temperature
at startup
Values (Range)
Unit
-100.0...9999.9
°C
0.00...99.99
0...60000
s
0...60000
s
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
The calculated temperature of
the protected object
The calculated temperature of
the protected object relative to
the trip level
Estimated time to trip
Estimated time to deactivate
BLK_CLOSE
Status
379