Section 3
Basic functions
Table 18:
General system settings
Parameter
Values (Range)
Rated frequency
1=50Hz
2=60Hz
Phase rotation
1=ABC
2=ACB
Blocking mode
1=Freeze timer
2=Block all
3=Block TRIP
output
1)
Bay name
Phase order mode
1=ABC
2=BCA
3=CAB
4=ACB
5=CBA
6=BAC
IDMT Sat point
10...50
1) Used in the protection relay's main menu header and as part of the disturbance recording identification
2) Depending on the product variant
58
Table 16:
DIAGLCCH1 Output signals
Name
Values
CHLIV
True
False
REDCHLIV
True
False
Table 17:
XGGIO90 Output signals
Name
Values
ETHLNK1
Up
Down
ETHLNK2
Up
Down
ETHLNK3
Up
Down
Unit
Step
I/I>
1
Description
Status of LAN A in HSR and PRP mode. When switch is
in "HSR" or "PRP" mode, value is "True" if the protection
relay is receiving supervision frames from LAN A. When
the switch is in "Normal" mode, value is "True" if the
protection relay is receiving Ethernet frames.
Status of LAN B in HSR and PRP mode. When switch is
in "HSR" or "PRP" mode, value is "True" if the protection
relay is receiving supervision frames from LAN B.
Disabled if
Switch mode is "Normal".
Description
Status of Ethernet link 1
Status of Ethernet link 2
Status of Ethernet link 3
Default
Description
1=60Hz
Rated frequency of the network
1=ABC
Phase rotation order
1=Freeze timer
Behavior for function BLOCK inputs
Bay name in system
2)
REF620
1=ABC
Selection for phase connection order
50
Overcurrent IDMT saturation point
1MAC504801-IB E
620 series ANSI
Technical Manual