Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.13.7
Table 211:
37 Group settings
Parameter
Values (Range)
Current block value
0.00...0.50
Pickup value
0.01...1.00
Trip delay time
50...200000
Table 212:
37 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Operation mode
1=Three Phase
2=Single Phase
Reset delay time
0...60000
4.1.13.8
266
Table 210:
37 Output signals
Name
Type
TRIP
BOOLEAN
TRIP_A
BOOLEAN
TRIP_B
BOOLEAN
TRIP_C
BOOLEAN
PICKUP
BOOLEAN
PICKUP_A
BOOLEAN
PICKUP_B
BOOLEAN
PICKUP_C
BOOLEAN

Settings

Unit
Step
xIn
0.01
xIn
0.01
ms
10
Unit
Step
ms
1

Monitored data

Table 213:
37 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
37
Enum
Description
Trip
Trip phase A
Trip phase B
Trip phase C
Pickup
Pickup phase A
Pickup phase B
Pickup phase C
Default
Description
0.10
Low current setting to block internally
0.50
Current setting to pickup
2000
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
1=Three Phase
Number of phases needed to pickup
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Status
620 series ANSI
Technical Manual