ABB RELION 620 Series Technical Manual page 859

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
12.2.2
620 series ANSI
Technical Manual
Reset in inverse-time modes
The user can select the reset characteristics by using the Type of reset curve setting.
Table 613:
Values for reset mode
Setting name
Type of reset curve
Immediate reset
If the Type of reset curve setting in a drop-off case is selected as "Immediate", the inverse
timer resets immediately.
Definite time reset
The definite type of reset in the inverse-time mode can be achieved by setting the Type of
reset curve parameter to "Def time reset". As a result, the trip inverse-time counter is
frozen for the time determined with the Reset delay time setting after the current drops
below the set Pickup value, including hysteresis.The integral sum of the inverse-time
counter is reset, if another pickup does not occur during the reset delay.
If the Type of reset curve setting is selected as "Def time reset", the current
level has no influence on the reset characteristic.
Inverse reset
Inverse reset curves are available only for ANSI and user-programmable
curves. If you use other curve types, immediate reset occurs.
Standard delayed inverse reset
The reset characteristic required in ANSI (IEEE) inverse-time modes is provided by
setting the Type of reset curve parameter to "Inverse reset". In this mode, the time delay
for reset is given with the following formula using the coefficient D, which has its values
defined in the table below.
D
[ ] =
t s
k
2
I
 −
1
>
I
A060817 V3 EN
General function block features
Possible values
1=Immediate
2=Def time reset
3=Inverse reset
Section 12
(Equation 110)
853

Advertisement

Table of Contents
loading

Table of Contents