Timer characteristics

67/51N and 67/50N supports both DT and IDMT characteristics. The user can select the
timer characteristics with the Operating curve type setting.
The protection relay provides 16 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. In addition to this,
a user programmable curve can be used if none of the standard curves are applicable. The
user can choose the DT characteristic by selecting the Operating curve type values "ANSI
Def. Time" or "IEC Def. Time". The functionality is identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages.
Table 158:
Timer characteristics supported by different stages
Operating curve type
(1) ANSI Extremely Inverse
(2) ANSI Very Inverse
(3) ANSI Normal Inverse
(4) ANSI Moderately Inverse
(5) ANSI Definite Time
(6) Long Time Extremely Inverse
(7) Long Time Very Inverse
(8) Long Time Inverse
(9) IEC Normal Inverse
(10) IEC Very Inverse
(11) IEC Inverse
(12) IEC Extremely Inverse
(13) IEC Short Time Inverse
(14) IEC Long Time Inverse
(15) IEC Definite Time
(17) User programmable curve
(18) RI type
(19) RD type
For a detailed description of the timers, see the
features
section in this manual.