ABB RELION 620 Series Technical Manual page 226

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
220
Min forward angle
Non-operating area
80 deg
70 deg
Max reverse angle
3% nominal
amplitude
1% nominal
amplitude
GUID-EFC9438D-9169-4733-9BE9-6B343F37001A-ANSI V1 EN
Figure 100:
Operating characteristic for phase angle classic 80
Non-
operating
area
-90
-75
GUID-49D23ADF-4DA0-4F7A-8020-757F32928E60-ANSI V1 EN
Figure 101:
Phase angle classic 80 amplitude
Phase angle 88
The operation criterion phase angle 88 is selected with the Operation mode setting using
the value "Phase angle 88".
-V
0
RCA
Forward
area
I
0
Backward
area
I
I
/ % of
n
0
10
Min forward angle
9
8
Forward
7
area
6
5
4
3
2
1
-60
-45
-30
-15
0
15
1MAC504801-IB E
Max forward angle
Min reverse angle
80 deg
3% of
70 deg
1% of
30
45
60
75
90
620 series ANSI
Technical Manual
70 deg
80 deg
I
n
I
n