Table 12:
Binary input settings
Parameter
Values (Range)
Threshold voltage
18...176
Input osc. level
2...50
Input osc. hyst
2...50
Table 13:
Ethernet front port settings
Parameter
Values (Range)
IP address
Mac address
Table 14:
Ethernet rear port settings
Parameter
Values (Range)
IP address
Subnet mask
Default gateway
Mac address
Table 15:
Redundancy settings
Parameter
Values (Range)
Switch mode
Normal
HSR
PRP
620 series ANSI
Technical Manual
To avoid communication errors with PCM600 while authentication is
enabled, ensure that appropriate credentials are used for the specific
action. Confirm that the password in the IED properties is valid for the
action attempted.
Unit
Step
Default
Vdc
2
18
events/s
1
30
events/s
1
10
Unit
Step
Default
192.168.0.254
XX-XX-XX-XX-
XX-XX
Unit
Step
Default
192.168.2.10
255.255.255.0
192.168.2.1
XX-XX-XX-XX-
XX-XX
Unit
Step
Default
Normal
Basic functions
Description
Binary input threshold voltage
Binary input oscillation suppression threshold
Binary input oscillation suppression hysteresis
Description
IP address for front port (fixed)
Mac address for front port
Description
IP address for rear port(s)
Subnet mask for rear port(s)
Default gateway for rear port(s)
Mac address for rear port(s)
Description
Mode selection for Ethernet switch on
Redundant communication modules. The
"Normal" mode is used with normal and Self-
healing Ethernet topologies.