Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Values (Range)
Curve parameter E
0.0...1.0
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
Pol signal Sel
1=Measured VG
2=Calculated V0
3=Neg. seq. volt.
1) The value of In is determined by the
Current (Io, CT)/Secondary current. If
Secondary current, since I0 is calculated by summing the phase currents.
4.1.5.12
230
Unit
Step
I0 signal Sel setting. If I0 signal Sel = Measured IG, then In is the value set in Configuration/Analog inputs/
I0 signal Sel = Calculated I0, then In is the value set in Configuration/Analog inputs/Current (3I, CT)/

Monitored data

Table 171:
67/51N Monitored data
Name
Type
FAULT_DIR
Enum
PICKUP_DUR
FLOAT32
DIRECTION
Enum
ANGLE_RCA
FLOAT32
ANGLE
FLOAT32
I_OPER
FLOAT32
67/51N
Enum
Default
Description
1.0
Parameter E for customer programmable
curve
2=Calculated I0
Selection for used Io signal
2=Calculated V0
Selection for used polarization signal
Values (Range)
Unit
0=unknown
1=forward
2=backward
3=both
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
-180.00...180.00
deg
-180.00...180.00
deg
0.00...40.00
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
1)
Description
Detected fault direction
Ratio of pickup time / trip time
Direction information
Angle between polarizing and
operating quantity
Angle between operating
angle and characteristic angle
Calculated operating current
Status
620 series ANSI
Technical Manual