Signals; Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 7
Measurement functions
7.1.10.3
7.1.10.4
Table 493:
P, E Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Power unit Mult
3=Kilo
6=Mega
Energy unit Mult
3=Kilo
6=Mega
Active power Dir
1=Forward
2=Reverse
Reactive power Dir
1=Forward
2=Reverse
Forward Wh Initial
0...999999999
Reverse Wh Initial
0...999999999
Forward VArh Initial
0...999999999
Reverse VArh Initial
0...999999999
654

Signals

Table 492:
P, E Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
V_A
SIGNAL
V_B
SIGNAL
V_C
SIGNAL
RSTACM
BOOLEAN

Settings

Unit
Step
1
1
1
1
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Phase A voltage
0
Phase B voltage
0
Phase C voltage
0=False
Reset of accumulated energy reading
Default
Description
1=enable
Operation Disable / Enable
3=Kilo
Unit multiplier for presentation of the power
related values
3=Kilo
Unit multiplier for presentation of the energy
related values
1=Forward
Direction of active power flow: Forward,
Reverse
1=Forward
Direction of reactive power flow: Forward,
Reverse
0
Preset Initial value for forward active energy
0
Preset Initial value for reverse active energy
0
Preset Initial value for forward reactive energy
0
Preset Initial value for reverse reactive energy
1MAC504801-IB E