Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.5.3.7
Table 329:
49M Group settings
Parameter
Values (Range)
Overload factor
1.00...1.20
Alarm thermal value
50.0...100.0
Restart thermal Val
20.0...80.0
Negative Seq factor
0.0...10.0
Weighting factor p
20.0...100.0
Time constant normal
80...4000
Time constant start
80...4000
Time constant stop
80...8000
Env temperature mode
1=FLC Only
2=Use input
3=Set Amb Temp
Env temperature Set
-20.0...70.0
Table 330:
49M Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Rated current
0.30...2.00
Initial thermal Val
0.0...100.0
620 series ANSI
Technical Manual
Table 328:
49M Output signals
Name
Type
TRIP
BOOLEAN
ALARM
BOOLEAN
BLK_RESTART
BOOLEAN

Settings

Unit
Step
0.01
%
0.1
%
0.1
0.1
%
0.1
s
1
s
1
s
1
°C
0.1
Unit
Step
xIn
0.01
%
0.1
Description
Trip
Thermal Alarm
Thermal overload indicator, to inhibit restart
Default
Description
1.05
Overload factor (k)
95.0
Thermal level above which function gives an
alarm
40.0
Thermal level above which function inhibits
motor restarting
6
Heating effect factor for negative sequence
current
50.0
Weighting factor (p)
320
Motor time constant during the normal
operation of motor
320
Motor time constant during the start of motor
500
Motor time constant during the standstill
condition of motor
1=FLC Only
Mode of measuring ambient temperature
40.0
Ambient temperature used when no external
temperature measurement available
Default
Description
5=disable
Operation Disable / Enable
1.00
Rated current (FLC) of the motor
74.0
Initial thermal level of the motor
Section 4
Protection functions
403