Section 7
Measurement functions
7.1.7.4
Table 480:
VG Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Measurement mode
1=RMS
2=DFT
V Hi high limit res
0.00...4.00
V high limit res
0.00...4.00
V deadband res
100...100000
7.1.7.5
7.1.7.6
7.1.8
7.1.8.1
648
Settings
Unit
Step
xVn
xVn
Monitored data
Table 481:
VG Monitored data
Name
Type
VG-kV
FLOAT32
Technical data
Table 482:
VG Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Sequence current measurement I1, I2, I0
Identification
Function description
Sequence current measurement
Default
Description
1=enable
Operation Disable / Enable
2=DFT
Selects used measurement mode
0.20
High alarm voltage limit
0.05
High warning voltage limit
10000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Values (Range)
Unit
0.00...4.00
xVn
Value
Depending on the frequency of the measured
current: f/f
= ±2 Hz
n
±0.5% or ±0.002 × V
DFT: -50 dB at f = n × f
RMS: No suppression
IEC 61850
IEC 60617
identification
identification
CSMSQI
I1, I2, I0
1MAC504801-IB E
Description
Measured residual voltage
n
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
I1, I2, I0
620 series ANSI
Technical Manual