Section 4
Protection functions
4.3.2.7
Table 276:
81LSH Group settings
Parameter
Values (Range)
Load shed mode
1=Freq<
6=Freq< OR df/dt
8=Freq< AND df/dt
Restore mode
1=Disabled
2=Auto
3=Manual
Pickup value Freq
0.800...1.200
Pickup value df/dt
-0.200...-0.005
Trip Tm Freq
80...200000
Trip Tm df/dt
120...200000
Restore pickup Val
0.800...1.200
Restore delay time
80...200000
Table 277:
81LSH Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
4.3.2.8
338
Name
Type
ST_FRG
BOOLEAN
RESTORE
BOOLEAN
ST_REST
BOOLEAN

Settings

Unit
Step
xFn
0.001
xFn /s
0.005
ms
10
ms
10
xFn
0.001
ms
10
Unit
Step
ms
1

Monitored data

Table 278:
81LSH Monitored data
Name
Type
PICKUP_DUR
FLOAT32
81LSH
Enum
Description
Pick-Up signal for high df/dt detection
Restore signal for load restoring purposes
Restore frequency attained and restore timer started
Default
Description
1=Freq<
Set the operation mode for load shedding
function
1=Disabled
Mode of operation of restore functionality
0.975
Frequency setting/pickup value
-0.010
Setting of frequency gradient for df/dt detection
200
Time delay to trip for under frequency stage
200
Time delay to trip for df/dt stage
0.998
Restore frequency setting value
300
Time delay to restore
Default
Description
5=disable
Operation Disable / Enable
50
Time delay after which the definite timers will
reset
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Pickup duration
Status
620 series ANSI
Technical Manual