Figure 316:
Typical motor-starting and capability curves
Setting of Cumulative time Lim
Cumulative time Lim is calculated by
t
=
(
n
− × +
) 1
t margin
si
GUID-0214B677-48D0-4DD4-BD1E-67BA9FD3C345 V1 EN
n
specified maximum allowed number of motor start-ups
t
start-up time of the motor (in seconds)
margin safety margin (~10...20 percent)
Setting of Counter Red rate
Counter Red rate is calculated by
t
t
=
s
t
reset
GUID-E7C44256-0F67-4D70-9B54-1C5042A151AF V1 EN
t
specified start time of the motor in seconds
t
duration during which the maximum number of motor start-ups stated by the manufacturer can be
reset
made; time in hours
Section 6
Supervision functions
(Equation 93)
(Equation 94)
619