Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.11.4
Table 50:
RTD input settings
Parameter
Values (Range)
Input mode
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
Input maximum
0...2000
Input minimum
0...2000
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
110
Name
Type
AI_VAL3
FLOAT32
AI_VAL4
FLOAT32
AI_VAL5
FLOAT32
AI_VAL6
FLOAT32
AI_VAL7
FLOAT32
AI_VAL8
FLOAT32

Settings

Unit
Step
1
1
1
1
1
1
1
1
1
Description
RTD input, Connectors 9-10-15c, instantaneous value
RTD input, Connectors 11-12-15c, instantaneous value
RTD input, Connectors 13-14-15c, instantaneous value
RTD input, Connectors 17-18-16c, instantaneous value
RTD input, Connectors 19-20-16c, instantaneous value
RTD input, Connectors 21-22-16c, instantaneous value
Default
Description
1=Not in use
Analogue input mode
2000
Maximum analogue input value for mA or
resistance scaling
0
Minimum analogue input value for mA or
resistance scaling
1=Dimensionless
Selected unit for output value format
10000.0
Maximum output value for scaling and
supervision
-10000.0
Minimum output value for scaling and
supervision
10000.0
Output value high alarm limit for supervision
10000.0
Output value high warning limit for supervision
-10000.0
Output value low warning limit for supervision
-10000.0
Output value low alarm limit for supervision
1000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
1MAC504801-IB E
620 series ANSI
Technical Manual