ABB RELION 620 Series Technical Manual page 770

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 9
Control functions
9.3.7
Table 548:
25 Group settings
Parameter
Values (Range)
Live dead mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
Difference voltage
0.01...0.50
Difference frequency
0.001...0.100
Difference angle
5...90
Table 549:
25 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Synchro check mode
1=Off
2=Synchronous
3=Asynchronous
Control mode
1=Continuous
2=Command
Dead line value
0.1...0.8
Live line value
0.2...1.0
Dead bus value
0.1...0.8
Live bus value
0.2...1.0
Close pulse
200...60000
Max energizing V
0.50...1.15
Phase shift
-180...180
Minimum Syn time
0...60000
Table continues on next page
764
Name
Type
CMD_FAIL_AL
BOOLEAN
LLDB
BOOLEAN
LLLB
BOOLEAN
DLLB
BOOLEAN
DLDB
BOOLEAN
Settings
Unit
Step
xVn
0.01
xFn
0.001
deg
1
Unit
Step
xVn
0.1
xVn
0.1
xVn
0.1
xVn
0.1
ms
10
xVn
0.01
deg
1
ms
10
Description
CB closing request failed
Live Line, Dead Bus
Live Line, Live Bus
Dead Line, Live Bus
Dead Line, Dead Bus
Default
Description
1=Both Dead
Energizing check mode
0.05
Maximum voltage difference limit
0.001
Maximum frequency difference limit
5
Maximum angle difference limit
Default
Description
5=disable
Operation Disable / Enable
2=Synchronous
Synchro check operation mode
1=Continuous
Selection of synchro check command or
Continuous control mode
0.2
Voltage low limit line for energizing check
0.5
Voltage high limit line for energizing check
0.2
Voltage low limit bus for energizing check
0.5
Voltage high limit bus for energizing check
200
Breaker closing pulse duration
1.05
Maximum voltage for energizing
180
Correction of phase difference between
measured U_BUS and U_LINE
0
Minimum time to accept synchronizing
1MAC504801-IB E
620 series ANSI
Technical Manual