Signals - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.1.3.8
620 series ANSI
Technical Manual
GUID-FA46F951-B376-4BC7-BCF4-F970C876CA7A-ANSI V1 EN
Figure 84:
Closed ring network topology where feeding lines are protected with
directional overcurrent protection relays

Signals

Table 123:
67/51P Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
2
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
1
V
SIGNAL
2
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
NON_DIR
BOOLEAN
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative phase sequence current
0
Phase to ground voltage A or phase to phase voltage AB
0
Phase to ground voltage B or phase to phase voltage BC
0
Phase to ground voltage C or phase to phase voltage
CA
0
Positive phase sequence voltage
0
Negative phase sequence voltage
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
0=False
Forces protection to non-directional
Section 4
Protection functions
181