Figure 347:
Concurrent dip and swell when Phase mode is "Single Phase"
In
Figure
348, one phase is in dip and two phases have a swell indication. For the Phase
Mode Dip value "Three Phase", the activation occurs only when all the phases are active.
Furthermore, both swell and dip variation event detections take place simultaneously. In
case of a concurrent voltage dip and voltage swell, both SWELLCNT and DIPCNT are
incremented by one.
Also
Figure 348
shows that for the Phase Mode value "Three Phase", two different time
moment variation event swell detections take place and, consequently, DIPCNT is
incremented by one but SWELLCNT is totally incremented by two. Both in
and
Figure 348
it is assumed that variation durations are sufficient for detections to take
place.