Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
Table 102:
50P-3 Group settings
Parameter
Values (Range)
Pickup value
1.00...40.00
Pickup value mult
0.8...10.0
Trip delay time
20...200000
Table 103:
50P-3 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Reset delay time
0...60000
4.1.1.10
156
Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
ms
1

Monitored data

Table 104:
51P Monitored data
Name
Type
PICKUP_DUR
FLOAT32
51P
Enum
Table 105:
50P-1/2 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
50P-1_2
Enum
Default
Description
4
Pickup value
1.0
Multiplier for scaling the pickup value
20
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Status
Description
Ratio of pickup time / trip time
Status
620 series ANSI
Technical Manual