1MAC504801-IB E
7.1.4.3
7.1.4.4
Table 465:
IA,IB,IC Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Measurement mode
1=RMS
2=DFT
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
A high high limit
0.00...40.00
A high limit
0.00...40.00
A low limit
0.00...40.00
A low low limit
0.00...40.00
A deadband
100...100000
620 series ANSI
Technical Manual
Signals
Table 463:
IA,IB,IC Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
Table 464:
IA,IB,IC Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
Settings
Unit
Step
xIn
xIn
xIn
xIn
Measurement functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block signal for all binary outputs
Description
High alarm
High warning
Low warning
Low alarm
Default
Description
1=enable
Operation Disable / Enable
2=DFT
Selects used measurement mode
1=1 out of 3
Number of phases required by limit supervision
2
High alarm current limit
2
High warning current limit
0.00
Low warning current limit
0.00
Low alarm current limit
2500
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)