Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.4.4.7
Table 302:
32U Group settings
Parameter
Values (Range)
Pickup value
0.01...2.00
Trip delay time
40...300000
Table 303:
32U Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Reset delay time
0...60000
Pol reversal
0=False
1=True
Disable time
0...60000
620 series ANSI
Technical Manual
Name
Type
DISABLE
BOOLEAN
BLK_TRIP
BOOLEAN
BLK_PICKUP
BOOLEAN
FR_TIMER
BOOLEAN
Table 301:
32U Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xSn
0.01
ms
10
Unit
Step
ms
10
ms
1000
Default
Description
FALSE
Signal to block the function during generator startup
FALSE
Block signal for operate output
FALSE
Block signal for start
FALSE
Freeze signal for timer
Description
Trip
Pickup
Default
Description
0.10
Pickup value
40
Trip delay time
Default
Description
5=disable
Opeartion
3=Pos Seq
Selection of power calculation method
20
Reset delay time
0=False
Reverse the definition of the power direction
0
Additional wait time after CB closing
Section 4
Protection functions
365