11.9.3
11.9.4
620 series ANSI
Technical Manual
Functionality
Time delay off (8 pcs) TOF can be used, for example, for a drop-off-delayed output related
to the input signal. The function contains eight independent timers. There is a settable
delay in the timer. Once the input is activated, the output is set immediately. When the
input is cleared, the output stays on until the time set with the Off delay time setting has
elapsed.
t
t
t
+dt
0
1
1
GUID-D45492E6-5FBC-420C-B1BF-B3A1F65ADF96 V1 EN
Figure 415:
Timer operation
Signals
Table 601:
TOF Input signals
Name
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
Table 602:
TOF Output signals
Name
Type
Q1
BOOLEAN
Q2
BOOLEAN
Q3
BOOLEAN
Q4
BOOLEAN
Q5
BOOLEAN
Table continues on next page
t
t
t
t
t
+dt
2
3
4
5
5
dt = Off delay time
Default
Description
0=False
Input 1 status
0=False
Input 2 status
0=False
Input 3 status
0=False
Input 4 status
0=False
Input 5 status
0=False
Input 6 status
0=False
Input 7 status
0=False
Input 8 status
Description
Output 1 status
Output 2 status
Output 3 status
Output 4 status
Output 5 status
Section 11
Other functions
819