Protection relay and functionality tests
Table 656:
Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance
test, all ports
Differential mode
Common mode
3 MHz/10 MHz/30 MHz burst
disturbance test, all ports
Common mode
Fast transient disturbance test, all
ports
Common mode/differential
mode
Radio frequency interference
tests
Electrostatic discharge test
Contact discharge
Air discharge
Surge immunity test
Communication
Other ports
Power frequency magnetic field
Voltage dips and short
interruptions
Power frequency immunity test,
binary inputs
Table continues on next page
Protection relay and functionality tests
Requirement
±2.5 kV
±2.5 kV
±2.5 kV
±4 kV
10 V/m (prior to modulation)
f = 80...2700 MHz (sweep and
keying test)
20 V/m (prior to modulation)
f = 80...1000 MHz (sweep and
keying test)
±8 kV
±15 kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m, >300 s
1000 A/m, 3 s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
150 V
, differential mode
rms
300 V
, common mode
rms
Section 16
Reference
IEC60255-22-1, Class III
IEC61000-4-18
IEEE37.90.1-2002
IEC61000-4-18, Level 3
IEC60255-22-4, Class A
IEC61000-4-4
IEEE37.90.1-2002
IEC60255-22-3
IEC61000-4-3
IEEE C37.90.2-2004
IEC60255-22-2
IEC61000-4-2, Class 4
IEEE C37.90.3-2001
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-22-7, class A