Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.2.6.8
Table 253:
24 Group settings
Parameter
Values (Range)
Pickup value
100...200
Operating curve type
5=ANSI DT
15=IEC DT
17=OvExt IDMT
Crv1
18=OvExt IDMT
Crv2
19=OvExt IDMT
Crv3
20=OvExt IDMT
Crv4
Time multiplier
0.1...100.0
Trip delay time
200...200000
620 series ANSI
Technical Manual
Name
Type
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
1
F
SIGNAL
BLOCK
BOOLEAN
Table 252:
24 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK_RESTART
BOOLEAN
COOL_ACTIVE
BOOLEAN

Settings

Unit
Step
%
1
0.1
ms
10
Default
Description
0
Phase-to-ground voltage A or phase-to-phase voltage
AB
0
Phase-to-ground voltage B or phase-to-phase voltage
BC
0
Phase-to-ground voltage C or phase-to-phase voltage
CA
0
Positive-phase sequence voltage
0
Measured frequency
0=False
Block signal
Description
Trip
Pickup
Signal for blocking reconnection of an overheated
machine
Signal to indicate machine is in cooling process
Default
Description
100
Over excitation pickup value
5=ANSI DT
Selection of time delay curve type
3.0
Time multiplier for Overexcitation IDMT curves
500
Trip delay time in definite- time mode
Section 4
Protection functions
311