ABB RELION 620 Series Technical Manual page 507

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Parameter
Values (Range)
Min Ng Seq A Zn3
0.10...10.00
Directional mode Zn4
2=Forward
3=Reverse
Z1 reach zone 4
0.10...1000.00
Z1 angle zone 4
10.0...90.0
Trip delay Zn4
30...200000
Ph Seq A check Zn4
0=False
1=True
Min Ps Seq A Zn4
0.10...10.00
Min Ng Seq A Zn4
0.10...10.00
Directional mode Zn5
2=Forward
3=Reverse
Z1 reach zone 5
0.10...1000.00
Z1 angle zone 5
10.0...90.0
Trip delay Zn5
30...200000
Ph Seq A check Zn5
0=False
1=True
Min Ps Seq A Zn5
0.10...10.00
Min Ng Seq A Zn5
0.10...10.00
Table 367:
21P Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Operation Zn1
1=enable
5=disable
Operation Zn2
1=enable
5=disable
Operation Zn3
1=enable
5=disable
Operation Zn4
1=enable
5=disable
Operation Zn5
1=enable
5=disable
620 series ANSI
Technical Manual
Unit
Step
Default
xIn
0.01
0.10
2=Forward
ohm
0.01
56.57
deg
0.1
45.0
ms
10
30
0=False
xIn
0.01
0.10
xIn
0.01
0.10
2=Forward
ohm
0.01
56.57
deg
0.1
45.0
ms
10
30
0=False
xIn
0.01
0.10
xIn
0.01
0.10
Unit
Step
Default
1=enable
1=enable
1=enable
1=enable
1=enable
1=enable
Protection functions
Description
Minimum Neg. seq. current for PP-loop, Zone 3
Directional mode, Zone Z4
Positive sequence zone reach, Zone Z4
Positive sequence line angle, Zone Z4
Time delay to trip of PP/3P-loops, Zone Z4
Enable optional phase sequence supervision
for PP/3P-loops, Zone Z4
Minimum Pos. seq. current for 3P-loop, Zone 4
Minimum Neg. seq. current for PP-loop, Zone 4
Directional mode, Zone Z5
Positive sequence zone reach, Zone Z5
Positive sequence line angle, Zone Z5
Time delay to trip of PP/3P-loops, Zone Z5
Enable optional phase sequence supervision
for PP/3P-loops, Zone Z5
Minimum Pos. seq. current for 3P-loop, Zone 5
Minimum Neg. seq. current for PP-loop, Zone 5
Description
Operation Disable / Enable
Operation Disable / Enable, Zone 1
Operation Disable / Enable, Zone Z2
Operation Disable / Enable, Zone Z3
Operation Disable / Enable, Zone Z4
Operation Disable / Enable, Zone Z5
Section 4
501

Advertisement

Table of Contents
loading

Table of Contents