1MAC504801-IB E
Parameter
Values (Range)
Maximum Syn time
100...6000000
Energizing time
100...60000
Closing time of CB
40...250
9.3.8
620 series ANSI
Technical Manual
Unit
Step
ms
10
ms
10
ms
10
Monitored data
Table 550:
25 Monitored data
Name
Type
ENERG_STATE
Enum
V_DIFF_MEAS
FLOAT32
FR_DIFF_MEAS
FLOAT32
PH_DIFF_MEAS
FLOAT32
V_DIFF_SYNC
BOOLEAN
PH_DIF_SYNC
BOOLEAN
FR_DIFF_SYNC
BOOLEAN
25
Enum
Default
Description
2000
Maximum time to accept synchronizing
100
Time delay for energizing check
60
Closing time of the breaker
Values (Range)
Unit
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
0.00...1.00
xVn
0.000...0.100
xFn
0.00...180.00
deg
0=False
1=True
0=False
1=True
0=False
1=True
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 9
Control functions
Description
Energization state of Line and
Bus
Calculated voltage amplitude
difference
Calculated voltage frequency
difference
Calculated voltage phase
angle difference
Voltage difference out of limit
for synchronizing
Phase angle difference out of
limit for synchronizing
Frequency difference out of
limit for synchronizing
Status
765