ABB RELION 620 Series Technical Manual page 413

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
620 series ANSI
Technical Manual
object are flowing into it. This causes the biasing current to be considerably smaller, which
makes the operation more sensitive during internal faults.
The traditional way for calculating the stabilized current is:
I
I
1
2
=
I
b
2
GUID-34FA472E-E419-4A0E-94A3-238D7A3CE5ED V1 EN
The module calculates the bias current for all three phases.
Through-fault detection
Through-fault (TF) detection module is for detecting whether the fault is external, that is,
going through, or internal. This information is essential for ensuring the correct operation
of the protection in case of the CT saturation.
In a through-fault situation, CTs can saturate because of a high fault current
magnitude. Such AC saturation does not happen immediately when the fault begins.
Thus, the TF module sees the fault as external because the bias current is high but the
differential current remains low. If the AC saturation then occurs, a CT saturation-
based blocking is allowed to work to prevent tripping.
Normally, the phase angle between the machine neutral and line side CTs is 180
degrees. If an internal fault occurs during a through fault, an angle less than 50
degrees clearly indicates an internal fault and the TF module overrules, that is,
deblocks the presence of any blocking due to CT saturation.
CT saturation-based blocking
Higher currents during the motor startup or abnormally high magnetizing currents at an
overvoltage (transformer-fed motor) or an external fault may saturate the current
transformers. The uneven saturation of the star and line side CTs (for example, due to
burden differences) may lead to a differential current which can cause a differential
protection to trip. This module blocks the operation of 87M biased low stage internally in
case of the CT saturation. Once the blocking is activated, it is held for a certain time after
the blocking conditions have ceased to be fulfilled.
DC component detection
On detection of a DC component, the function temporarily desensitizes the differential
protection. The functioning of this module depends on the DC restrain Enable setting.
The DC components are continuously extracted from the three instantaneous differential
currents. The highest DC component of all three is taken as a kind of DC restraint in a
sense that the highest effective, temporary sensitivity of the protection is temporarily
decreased as a function of this highest DC offset. The calculated DC restraint current is not
allowed to decay (from its highest ever measured value) faster than with a time constant
of one second. The value of the temporarily effective sensitivity limit is limited upwards
Section 4
Protection functions
(Equation 33)
407

Advertisement

Table of Contents
loading

Table of Contents