ABB RELION 620 Series Technical Manual page 550

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 5
Protection-related functions
5.3.7
Table 398:
86/94 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Trip pulse time
20...60000
Trip output mode
1=Non-latched
2=Latched
3=Lockout
5.3.8
5.4
5.4.1
5.4.2
544
Settings
Unit
Step
ms
1
Monitored data
Table 399:
86/94 Monitored data
Name
Type
86/94
Enum
High-impedance fault detection HIZ
Identification
Function description
High-impedance fault detection
Function block
GUID-820AC478-7007-4A68-82D7-3A01542EDC40 V2 EN
Figure 262:
Function block
Default
Description
1=enable
Operation Disable / Enable
150
Minimum duration of trip output signal
1=Non-latched
Select the operation mode for trip output
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
IEC 61850
IEC 60617
identification
identification
PHIZ
PHIZ
1MAC504801-IB E
Description
Status
ANSI/IEEE C37.2
device number
HIZ
620 series ANSI
Technical Manual