Settings; Monitored Data; Technical Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.6.4.9
Table 358:
87 Group settings
Parameter
Values (Range)
Trip value
1...200
Minimum trip time
20...300000
Table 359:
87 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
4.6.4.10
4.6.4.11
620 series ANSI
Technical Manual

Settings

Unit
Step
%In
1
ms
10
Unit
Step
ms
10

Monitored data

Table 360:
87 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
87
Enum

Technical data

Table 361:
87A, 87B, 87C Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
I
Fault
value
I
Fault
value
Reset time
Table continues on next page
Default
Description
5
Trip value, percentage of the nominal current
20
Minimum trip time
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the current
measured: f
±1.5% of the set value or ±0.002 × I
Minimum
Pickup
= 2.0 × set
12 ms
Pickup
= 10 × set
10 ms
<40 ms
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Status
±2 Hz
n
n
Typical
Maximum
16 ms
24 ms
12 ms
14 ms
487