Signals; Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.6.1.6
4.6.1.7
Table 335:
87M Group settings
Parameter
Values (Range)
Low trip value
5...30
High trip value
100...1000
Slope section 2
10...50
End section 1
0...100
End section 2
100...300
DC restrain enable
0=False
1=True
620 series ANSI
Technical Manual

Signals

Table 333:
87M Input signals
Name
Type
I_A1
SIGNAL
I_B1
SIGNAL
I_C1
SIGNAL
I_A2
SIGNAL
I_B2
SIGNAL
I_C2
SIGNAL
BLOCK
BOOLEAN
BLK_OPR_LS
BOOLEAN
BLK_OPR_HS
BOOLEAN
Table 334:
87M Output signals
Name
Type
TRIP
BOOLEAN
OPR_LS
BOOLEAN
OPR_HS
BOOLEAN
INT_BLKD
BOOLEAN

Settings

Unit
Step
%Ir
1
%Ir
10
%
1
%Ir
1
%Ir
1
Default
Description
0
Current ID for getting current values for phase A,
winding 1
0
Current ID for getting current values for phase B,
winding 1
0
Current ID for getting current values for phase C,
winding 1
0
Current ID for getting current values for phase A,
winding 2
0
Current ID for getting current values for phase B,
winding 2
0
Current ID for getting current values for phase C,
winding 2
0=False
Block signal for activating the blocking mode
0=False
Blocks trip outputs from biased stage
0=False
Blocks trip outputs from instantaneous stage
Description
Trip
Trip from low set
Trip from high set
Internal block status
Default
Description
5
Basic setting for the stabilized stage pickup
500
Instantaneous stage trip value
30
Slope of the second line of the operating
characteristics
50
Turn-point between the first and the second
line of the operating characteristics
150
Turn-point between the second and the third
line of the operating characteristics
0=False
Setting for enabling DC restrain feature
Section 4
Protection functions
419