Common signals
The VALID output indicates the validity of received GOOSE data, which means in case
of valid, that the GOOSE communication is working and received data quality bits (if
configured) indicate good process data. Invalid status is caused either by bad data quality
bits or GOOSE communication failure. See IEC 61850 engineering guide for details.
The OUT output passes the received GOOSE value for the application. Default value (0)
is used if VALID output indicates invalid status. The IN input is defined in the GOOSE
configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or PCM600.

GOOSERCV_BIN function block

Function block

GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 40:
Function block

Functionality

The GOOSERCV_BIN function is used to connect the GOOSE binary inputs to the
application.

Signals

Table 53:
GOOSERCV_BIN Input signals
Name
Type
IN
BOOLEAN
Table 54:
GOOSERCV_BIN Output signals
Name
Type
OUT
BOOLEAN
VALID
BOOLEAN
Basic functions
Default
Description
0
Input signal
Description
Output signal
Output signal