Function Block; Functionality; Operation Principle - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.6.2.2
4.6.2.3
4.6.2.4
422

Function block

87T
I_A1
TRIP
I_B1
OPR_LS
I_C1
OPR_HS
I_A2
BLKD2H
I_B2
BLKD5H
I_C2
BLKDWAV
I_A3
I_B3
I_C3
BLOCK
BLK_OPR_LS
BLK_OPR_HS
GUID-2B005C29-6D03-41EF-8CA8-FC4E8D5BB3FB V2 EN
Figure 192:
Function block

Functionality

The transformer differential protection 87T provides up to three three-phase current sets
or restraints designed for protection of two-winding or three-winding transformers and
generator-transformer blocks with a possibility to have two three-phase current sets either
on the winding 1 or winding 2 side in case of two-winding transformer protection. The
function includes a biased low stage and an instantaneous high stage.
The biased low stage provides a fast clearance of faults while remaining stable with high
currents passing through the protected zone increasing errors on current measuring. The
second harmonic restraint, together with waveform-based algorithms, ensures that the low
stage does not trip due to the transformer inrush currents. The fifth harmonic restraint
ensures that the low stage does not trip on apparent differential current caused by a
harmless transformer overexcitation.
The instantaneous high stage provides a very fast clearance of severe faults with a high
differential current regardless of their harmonics.
The setting characteristic can be set more sensitive with tap changer position
compensation. The correction of transformation ratio due to changes in tap position is
done automatically based on the tap changer status information provided to the function
through input.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of transformer differential protection can be described with a module
diagram. All the modules in the diagram are explained in the next sections.
1MAC504801-IB E
620 series ANSI
Technical Manual