Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Table 51:
mA input settings
Parameter
Values (Range)
Input mode
1=Not in use
5=0..20mA
Input maximum
0...20
Input minimum
0...20
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
3.11.5
620 series ANSI
Technical Manual
Unit
Step
mA
1
mA
1
1
1
1
1
1
1
1

Monitored data

Table 52:
RTD/mA monitored data
Name
Type
AI_DB1
FLOAT32
AI_RANGE1
Enum
AI_DB2
FLOAT32
AI_RANGE2
Enum
AI_DB3
FLOAT32
Table continues on next page
Default
Description
1=Not in use
Analogue input mode
20
Maximum analogue input value for mA or
resistance scaling
0
Minimum analogue input value for mA or
resistance scaling
1=Dimensionless
Selected unit for output value format
10000.0
Maximum output value for scaling and
supervision
-10000.0
Minimum output value for scaling and
supervision
10000.0
Output value high alarm limit for supervision
10000.0
Output value high warning limit for supervision
-10000.0
Output value low warning limit for supervision
-10000.0
Output value low alarm limit for supervision
1000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Values (Range)
Unit
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
Section 3
Basic functions
Description
mA input, Connectors 5-6,
reported value
mA input, Connectors 5-6,
range
mA input, Connectors 7-8,
reported value
mA input, Connectors 7-8,
range
RTD input, Connectors
9-10-15c, reported value
111