Section 4
Protection functions
4.1.12.7
Table 206:
51LR Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
0.10...10.00
Trip delay time
100...120000
Reset delay time
0...60000
4.1.12.8
4.1.12.9
262

Settings

Unit
Step
xIn
0.01
ms
10
ms
1

Monitored data

Table 207:
51LR Monitored data
Name
Type
PICKUP
BOOLEAN
PICKUP_DUR
FLOAT32
51LR
Enum

Technical data

Table 208:
51LR Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Default
Description
1=enable
Operation Disable / Enable
2.50
Pickup value
2000
Trip delay time
100
Reset delay time
Values (Range)
Unit
0=False
1=True
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
1MAC504801-IB E
Description
Pickup
Ratio of pickup time / trip time
Status
n
620 series ANSI
Technical Manual