Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 10
Recording functions
Table 571:
FLO Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Line length
0.0...300.0
R1
0.000...20.000
X1
0.000...30.000
R0
0.000...20.000
X0
0.000...30.000
10.2.7
790
Unit
Step
0.1
ohm
0.001
ohm
0.001
ohm
0.001
ohm
0.001

Monitored data

Table 572:
FLO Monitored data
Name
Type
FLT_DIST
FLOAT32
FLT_LOOP
Enum
FLT_R
FLOAT32
XF_LOOP
FLOAT32
TIME_FLT_LOC
Timestamp
FLO
Enum
Default
Description
5=disable
Operation Disable / Enable
100.0
Length of the Line in miles or Km
1.000
Pos Seq Resistance in ohms/(miles or Km)
2.000
Pos seq reactance in ohms/(miles or Km)
0.010
Pos Seq Resistance in ohms/(miles or Km)
1.000
Zero Seq Reactance in ohms/(miles or Km)
Values (Range)
Unit
0.00...9999.00
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-1=ABG Fault
-2=BCG Fault
-3=CAG Fault
-4=ABCG Fault
0=No fault
0.00...999.00
ohm
0.00...9999.00
ohm
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Fault Distance
Fault Loop
FaultResistance
Loop Reactance
Time stamp
Status
620 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents