ABB RELION 620 Series Technical Manual page 753

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Parameter
Values (Range)
Dsr time shot 2
0...10000
Dsr time shot 3
0...10000
Dsr time shot 4
0...10000
Terminal priority
1=None
2=Low (follower)
3=High (master)
Synchronisation set
0...127
Auto wait time
0...60000
Auto lockout reset
0=False
1=True
Protection crd limit
1...5
Protection crd mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
Auto initiation cnd
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
Tripping line
0...63
Control line
0...63
Enable shot jump
0=False
1=True
CB closed Pos status
0=False
1=True
Fourth delay in SOTF
0=False
1=True
First reclose time
0...300000
Second reclose time
0...300000
Third reclose time
0...300000
Table continues on next page
620 series ANSI
Technical Manual
Unit
Step
ms
100
ms
100
ms
100
ms
10
ms
10
ms
10
ms
10
Control functions
Default
Description
0
Discrimination time
for second reclosing
0
Discrimination time
for third reclosing
0
Discrimination time
for fourth reclosing
1=None
Terminal priority
0
Selection for
synchronizing
requirement for
reclosing
2000
Wait time for
reclosing condition
fullfilling
0=False
Automatic lockout
reset
2
Protection
coordination shot
limit
1=No condition
Protection
coordination mode
2=When sync fails
Auto initiation
condition
19
Tripping line, defines
INIT inputs which
cause OPEN_CB
activation
19
Control line, defines
INIT inputs which are
protection signals
0=False
Enable shot jumping
0=False
Circuit breaker
closed position status
0=False
Sets 4th delay into
use for all DEL_INIT
signals during SOTF
500
Dead time for CBB1
1000
Dead time for CBB2
2000
Dead time for CBB3
Section 9
747