1MRS757644 F
4.1.9.9
4.1.9.10
4.1.10
4.1.10.1
4.1.10.2
620 series
Technical Manual
Technical data
Table 355:
LOFLPTUC Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Technical revision history
Table 356:
LOFLPTUC Technical revision history
Technical revision
B
C
Loss of phase, undercurrent PHPTUC
Identification
Function description
Loss of phase, undercurrent
Function block
GUID-ED7916D7-8083-4660-B274-252DA7DCB833 V1 EN
Figure 167:
Function block
Protection functions
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
Typically 300 ms
Typically 40 ms
Typically 1.04
<35 ms
±1.0% of the set value or ±20 ms
Change
Internal improvement
Internal improvement
IEC 61850
IEC 60617
identification
identification
PHPTUC
3I<
Section 4
n
ANSI/IEEE C37.2
device number
37
341