Bosch Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS Functional Description page 446

With integrated nc control
Table of Contents

Advertisement

15-4
EMD Module (EcoX-Bus)
Outputs
Number
Connections
External Power Supply
total
by group
Rated Voltage
Rated Current
maximum per output
maximum per group
maximum per module (16 DO)
Leakage Current
Maximum Switching Frequency
with Ohm load
with inductive load
Short-Circuit Diagnostic
Short-Circuit Protection
Electronic Isolation – Circuit Side
Conditions for Use
Ambient Temperature Allowed
Storage and Transport Temperature
max.
Max. Allowable Relative Humidity
Air Pressure during Operation
Protection Type
Special Requirements for Operation
U
B
I
B
Fig. 15-5: EMD Input/Output Module Data
ECODRIVE03-FL*-04VRS
16
triple-conductor
with power supply clamps 24 V, 0 V
and ground clamp
with power supply clamps for each
group of 8 outputs
V [DC]
24
A
0.5
4.0
8.0
mA
< 0.2
no short-circuit diagnostic possible
electronic, automatic re-start
no
°C
0° ... +55°
°C
-25° ... +70°
m over NN
2000
%
10 - 45, no condensation
hPa
86 ... 106
IP 20 according to EN 60529
/IEC 529
The unit can be used in locations
where dust, caustic steam, caustic
gases or ionized radiation can be
present, only if additional measures
are undertaken!
DOK-ECODR3-FL*-04VRS**-FK01-EN-P