Diagnostic Message Descriptions
12.3 Command Diagnostics C.. ., D. ..

C100 Communication phase 3 transition check

C200 Communication phase 4 transition check

C201 Invalid Parameters

C202 Parameter limit error

C203 Parameter calculation error

The C100 Communication phase 3 transition check command has
been activated.
Definition
The C200 Communication phase 4 transition check command has
been activated. A switch from Parameter Mode to Manual or Automatic.
"C2" Display
Cause:
Parameters needed to operate the drive in communications phase 4
(operating mode) are invalid.
Remedy:
Check parameters and make corrections.
Turn unit off and on
Check for correct firmware.
Cause:
Parameters needed to operate the drive in communications phase 4
mode (manual/automatic) exceed the minimum or maximum input values,
or the entered value cannot be processed.
Remedy:
Check parameters and make corrections.
Check for correct firmware.
Turn off and then on again. If this does not solve the problem:
Replace the unit.
Cause:
Parameters needed for phase 4 (operating mode) cannot be processed
as they are.
Remedy:
Check parameters and make corrections.
Check for correct firmware.
Turn off and then on again. If this does not solve the problem:
Replace the unit.
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P