Polling Query; Sis Protocol - Bosch Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS Functional Description

With integrated nc control
Table of Contents

Advertisement

10-46
Interface
Re-Initialize PLS

Polling Query

SIS Protocol

The PLS is initialized using the current PLS parameter data.
Format:
! s C I N I T N $ h h C R L F
Note:
The command is accepted only in Manual or Automatic Mode.
An answer of Yes occurs immediately after acceptance of the command.
A query, in the shortest possible format, which cyclically polls all of the
controls connected to the RS485 bus.
The query:
: s C R L F
is answered with:
: s n n n n C R L F
Meaning of the characters used:
nnnn =
Diagnostic Error Number (Hexadecimal)
See also Diagnostics, Chapter 12.
In preparation
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P