12-60
Diagnostic Message Descriptions
F- 0314 Instruction offset greater than 999
F- 0315 BCD selection incorrect
F- 0316 Systemcontrol Error
F- 0317 Serial I/O Error
The value for the instruction offset in the 'BIC' command is greater than
999.
Cause:
•
For constants:
•
For variables:
Remedy:
Re-save the command with valid values.
The value for the mode in the 'BIC' command is not within the range 0 to
1.
The real-time communication to the Fieldbus / BTV04 is interrupted.
Cause:
System control via the fieldbus or via the BTV04 is interrupted in 'Manual'
or 'Automatic' Mode.
Remedy:
•
BTV04:
•
Check grounding of all cables on the DKC.
•
Ground BTV04 housing.
•
Use shielded cables (Motor / Serial Interface).
•
Increase maximum cycle time in Parameter B009.
•
Possibly reduce the 'Answer Delay Time' value (Default = 4ms) in
the BTV04.
•
Fieldbus :
•
Ensure that the fieldbus card connector is correctly inserted.
•
Check the fieldbus cable for errors.
•
Check master.
The cyclic communication to the Fieldbus / BTV04 is interrupted for:
BTV04:
In 'Manual' or 'Automatic' Mode, and Standard system
control (B010), if only the 'serial inputs/outputs' in
Parameter B009 are activated.
Fieldbus:
In 'Automatic' Mode with serial system control or via the
EMD module (Parameter B010).
ECODRIVE03-FL*-04VRS
Data loss.
Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
DOK-ECODR3-FL*-04VRS**-FK01-EN-P