Error Message In The Firmware Loader - Bosch Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS Functional Description

With integrated nc control
Table of Contents

Advertisement

4-14
General Instructions for Start-Up

Error Message in the Firmware Loader

If a firmware update is performed via the serial interface (using the SIS
protocol), it is possible that the drive will generate error messages.
These messages are displayed both by DOLFI, as shown in the figure
below, and by the drive on its 7-segment display:
Fig. 4-7: Example: An illustration of a "Firmware was cleared" error
The table below lists the error messages:
SIS Error
7 Segment
Message
Display
Number
0x9002
dL / 00
0x9003
-
0x9004
-
0x9102
dL / 03
0x9103
-
0x9104
-
0x9200
dL / 06
0x9400
dL / 07
0x9402
dL / 0F
0x940A
dL / 08
0x960A
-
0x96E0
dL / 0b
0x96E1
dL / 0C
0x96FF
dL / 09
0x9701
dL / 0d
0x9702
dL / 0E
Fig. 4-8: SIS Errors in the Firmware Loader
ECODRIVE03-FL*-04VRS
Error Message:
Firmware was cleared
Loading not allowed in phase 3.
Loading not allowed in phase 4.
Firmware was cleared
Restart not allowed in phase 3
Restart not allowed in phase 4
Read error
Timeout during delete
Address range not in flash memory
Deletion possible only in loader
Programming possible only in loader
Error during flash memory verification
Timeout when programming flash memory
Error when writing to RAM
Wrong checksum
Wrong CRC32 checksum
DOK-ECODR3-FL*-04VRS**-FK01-EN-P