9-30
Parameters
AA19 Press: Time Monitoring
99 M2.02.2
Output Bit: "Timeout – Time expired."
Timeout in min.
00 = function inactive
Note:
The input bit "Press" in Parameter
programmed.
The press motion is tested using the falling edge of the feed angle (A116
Feed Angle Monitoring). In Automatic Mode and for the input bit "Press"
(AA12) = 1, the 1 Å 0 edge is monitored. If this edge does not transition
during the timeout preselected in the parameter, the following diagnostic
is issued: "A- 00 12 – Press Timeout" and the output bit programmed in
Parameter AA19 is set.
Via the function "Clear Error," the diagnostic and the output bit are
cleared. Thereafter, time monitoring restarts.
The following conditions clear the diagnostic and the output bit:
Fault, Manual Mode, NC Stop
ECODRIVE03-FL*-04VRS
M2, M3, M4
EMD
: Q3.00.0-Q3.03.7
DKC21.3 : Q0.00.4-Q0.01.3
DKC 3.3 : Q2.02.0-Q2.05.7
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
AA12 must be