ECODRIVE03-FL*-04VRS
12.7 NC Error Diagnostics F- .. ..
F- 0200 Parameter and automatic input simultaneously
F- 0201 Wrong phase transition
F- 0203 Target position < negative position limit
F- 0204 Target position > positive position limit
F- 0205 Stack overflow with JSR command
F- 0206 Stack overflow with RTS command
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
If the 'Parameters' input is activated in Automatic Mode, the following
error message is issued. The 'Automatic' input is not monitored in
Parameter Mode.
The phase transition in the drive, which is initiated through a mode
change from Manual/Automatic Mode to Parameter Mode or vice versa,
failed.
Cause:
There is a software error.
Remedy:
Please contact REXROTH Customer Service.
The target position pre-set in an NC feed command (POA, POI, PFA, PFI,
PSA or PSI) is less than the negative position limit.
The target position pre-set in an NC feed command (POA, POI, PFA, PFI,
PSA or PSI) is greater than the positive position limit.
The nesting for subroutine programming exceeds 16 levels.
Remedy:
•
Check program. Every program containing the JSR command that is
called must end with an RTS command.
•
It is possible that a JSR command was programmed without an RTS.
The nesting for subroutine programming is less than 0 levels.
Remedy:
•
Check program. Every program containing the JSR command that is
called must end with an RTS command.
•
It is possible that an RTS command was programmed without a JSR.
Diagnostic Message Descriptions
12-51