F- 0311 Stack correction value > 9
F- 0312 Select Parameter Mode
F- 0313 Jump interval > 99
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
•
B009:
No 'Serial inputs/outputs' are set in the parameters, but
'serial system control' is pre-selected in B010.
•
B014:
No 'EMD modules' are set in the parameters, but 'system
control via EMD module' is pre-selected in B010.
•
C011:
The reference distance is greater than A105 'Modulo
Value' for A100 Motion Type 'Rotary Table.'
•
C006:
The 'timeout duration' is set in the parameters, but the
press function is not activated in AA12.
The value for the correction of the subprogram stack level in the 'CST'
command is greater than 9.
Cause:
•
For constants:
•
For variables:
Remedy:
Re-save the command with valid values.
The error message "F- 03 10 – Parameter Error" was acknowledged.
Parameter Mode was not pre-selected.
Remedy:
Activate Parameter Mode and clear the error again. Then correct the
incorrect parameters.
The value for the jump interval in the 'BIC' command is greater than 99.
Cause:
•
For constants:
•
For variables:
Remedy:
Re-save the command with valid values.
Diagnostic Message Descriptions
Data loss.
Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Data loss.
Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
12-59