F- 0207 Invalid destination task number

F- 0208 Per mil value in ACC command > 999

F- 0209 Invalid value in FAK command

F- 0210 Feed angle loss

F- 0211 Torque > 500%
The number of the destination task in the JTK command is not within the
range 1 to 3.
The value for acceleration and/or deceleration is greater than 999 per mil.
Cause:
For constants:
For variables:
Remedy:
Re-save the command with valid values.
The value for the multiplication factor in the FAK command is not within
the range 0 to +1.999999.
Cause:
For constants:
For variables:
Remedy:
Re-save the command with valid values.
The signal at the input 'Feed angle monitoring' dropped off during a move.
See Parameter A116.
The value for at least one torque value in the MOM command is greater
than 500 percent.
Cause:
For constants:
For variables:
Remedy:
Re-save the command with valid values.
ECODRIVE03-FL*-04VRS
Data loss.
Value of the destination variable is too large.
Possibly caused by access to an incorrect
destination
variable
variables.
Data loss.
Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.
Data loss.
Value of the destination variable is too large or
negative. Possibly caused by access to an
incorrect destination variable when using indexed
variables.