Mp2100M Mode Switch Settings - YASKAWA MP2100 Series User Manual

Machine controller design and maintenance
Table of Contents

Advertisement

6 Basic System Operation

6.2.2 MP2100M Mode Switch Settings

6.2.2 MP2100M Mode Switch Settings
The mode switch pins are used to control the startup sequence for the MP2100M. The following table shows the
function of each pin on the switch.
Mode Switch 1 (S1)
No.
Name
1
TEST
2
MON
3
CNFG
4
INIT
5
SUP
6
STOP
7
SLOT0
8
SLOT1
* Set the CP number allocated to the communication process logic port. When using two or more
MP2100M, set a different CP number.
6-4
Status
Function
ON
System use
OFF
Normal operation
ON
System use
OFF
Normal operation
ON
Configuration mode
OFF
Normal operation
ON
Memory clear
OFF
Normal operation
ON
System use
OFF
Normal operation
ON
User program stopped
OFF
User program running
SLOT1
- SLOT0
 
ON
- ON
CP4
ON
- OFF
CP3
OFF
- ON
CP2
OFF
- OFF
CP1
Factory
Setting
OFF
Always leave set to OFF.
OFF
Always leave set to OFF.
OFF
Set to ON to execute self-configuration for
connect devices.
OFF
Set to ON to clear memory. If this switch is set
to OFF, the program stored in flash memory
will be executed. The S registers and M regis-
ters are cleared to 0.
OFF
Always leave set to OFF.
OFF
Set to ON to stop the user program executing
and perform program debugging.
OFF
Use to set CP number.
OFF
Details

Advertisement

Table of Contents
loading

This manual is also suitable for:

Japmc-mc2100Mp2100m seriesJapmc-mc2140

Table of Contents