(3) Motion Monitoring Parameters
(a) Drive Status
IW
00
IW
00
Bit 0
Bit 1
(b) Over Range Parameter Number
IW
01
Stores the number of a parameter set outside the range.
• Setting parameters: 0 to 999
• Fixed parameters: 1000 or higher
(c) Warning
IL
02
IL
02
Bit 1
Bit 2
Bit 4
(d) Alarm
IL
04
IL
04
Bit 5
(e) Motion Command Response Code
IW
08
Stores the motion command code for the command that is being executed.
Drive Status
Range
Motion Controller Operation Ready
Turns ON when the Run Mode (fixed parameter 0) is set to 0 (Normal Running).
OFF: Not ready for operation
ON: Ready for operation
Running (Servo ON)
OFF: Stopped
ON: Running (Servo ON)
Over Range Parameter Number
Range
0 to 65535
Warning
Range
Setting Parameter Error
OFF: In range
ON: Outside range
Fixed Parameter Error
OFF: In range
ON: Outside range
Motion Command Setting Error
OFF: Command setting normal
ON: Command setting error
Alarm
Range
Servo OFF
OFF: Servo ON
ON: Servo OFF
Servo Command Type Response
Range
0 to 65535
11.2 Motion Parameters