YASKAWA MP2100 Series User Manual page 333

Machine controller design and maintenance
Table of Contents

Advertisement

(6) Ladder Program for Infinite Length Axis Position Control
Ladder program for normal operation and for restarting the system is needed for absolute infinite length axis
position control when the simple absolute infinite length position control function is not used.
(a) Normal Operation
1. Check the status of the Zero Point Return (Setting) Completed bit.
Check to see if the Zero Point Return (Setting) Completed bit (monitoring parameter IW
ON. If it is, go to step 2. If it is not, it means that the pulse position at power OFF, encoder position at
power OFF and all position data was not settled. In that case, restart the system and set up the position
data again or execute the ZSET (zero point setting) motion command to settle the position data all over
from the start.
2. Save the modularized position at power OFF and absolute position at power OFF.
Use the ladder program to save the following monitoring parameters with high-speed scan timing at an M
register backed up by battery.
• Monitoring parameter: Absolute Position at Power OFF (All four words at IL
• Monitoring parameter: Modularized Position at Power OFF (All four words at IL
The M register that is used to save the above monitoring parameters is structured as shown below.
MW
MW
+1
ML
+2
ML
+4
ML
+6
ML
+8
ML
+10
ML
+12
ML
+14
ML
+16
Note: Two buffers are needed to save the absolute position and the modularized position at power
OFF because the program may be exited without settling position data at all four words if
power is turned OFF during the high-speed scan.
Bit 0
Toggle Buffer Enabled Flag (OFF: Disabled, ON: Enabled)
Bit 1
Toggle Buffer Selection Flag (OFF: Buffer 0, ON: Buffer 1)
Bit 2
Position Data Re-setup Request Flag (OFF: Complete, ON: Request)
Not used
Buffer 0
Monitoring parameter:
Absolute Position at
Monitoring parameter:
Modularized Position at
Buffer 1
Monitoring parameter:
Absolute Position at
Monitoring parameter:
Modularized Position at
10.3 Using an Absolute Encoder
Lower-place two words
Power OFF
(IL
5E
Upper-place two words
(IL
60
Lower-place two words
Power OFF
(IL
62
Upper-place two words
(IL
64
Lower-place two words
Power OFF
(IL
5E
Upper-place two words
(IL
60
Lower-place two words
Power OFF
(IL
62
Upper-place two words
(IL
64
0C, bit 5) is
5E to IL
60)
62 to IL
64)
)
)
)
)
)
)
)
10
)
10-21